Connecticut utility regulators have fined Connecticut Natural Gas $100,000 after a worker overpressurized a new residential gas line in Wethersfield during a safety test, then gave a state inspector a false explanation, according to regulators.
The Public Utilities Regulatory Authority also fined sister company Southern Connecticut Gas $50,000 over an improperly installed fitting in North Haven. PURA issued both notices of violation Oct. 26.
At its Wednesday meeting, PURA appointed Chairman Thomas Wiehl as presiding officer in both cases.
The Wethersfield incident occurred Aug. 5, when a PURA Gas Pipeline Safety Unit inspector was observing a CNG crew installing a service line to a home on Griswold Road.
As a crew member began testing the new plastic line with nitrogen, he increased the pressure without watching the gauges, according to PURA. The inspector saw the needle on a 200-pound-per-square-inch gauge spin nearly a full rotation past its maximum reading.
The worker shut off the nitrogen, removed the gauge and claimed it had been damaged during an earlier job. The crew’s foreman, who had not witnessed the incident, was preparing to tap the main and introduce natural gas into the line. The inspector stopped him.
A subsequent test showed the gauge was functioning accurately. A CNG supervisor later ordered the entire service line replaced.
CNG later told regulators the gauge had not been damaged on a previous job. PURA’s notice says the worker “lied about the manifold gauge being damaged.”
PURA cited CNG for three violations: exceeding the test pressure allowed under federal rules, failing to take every reasonable precaution to protect workers and the public, and breaking its own procedures, which cap test pressure for that type of pipe at 200 psi.
The North Haven incident occurred July 27, when a PURA inspector observed an SCG contractor crew reconnecting a home’s service line to a new gas main.
A worker installed an end cap on the old line but failed to push it far enough onto the pipe. The cap sat about three-quarters of an inch from the installation mark, twice the three-eighths-inch maximum allowed under the manufacturer’s instructions.
The worker remarked that he thought he had misjudged the mark. But he began releasing the tool holding back the gas before measuring the fitting, PURA said. The inspector ordered him to stop, and the crew replaced the cap.
Both penalties must be used to purchase residential methane detectors, which must be installed within 180 days in homes with indoor gas meters.
Any penalty money the utilities recover from contractors or insurers must be returned to customers. The companies also must obtain PURA approval in a future rate case before charging customers for repairs or other corrective work related to the violations.
Each company has 20 days from receiving its notice to request a hearing. Without one, the notice becomes a final order and the violations are deemed admitted.
“We take the matters raised in these notices seriously and remain committed to the safety of our customers, employees and communities,” said Angela Baccaro, spokesperson for CNG and SCG. “We are reviewing the circumstances surrounding the notices and will respond through the regulatory docket.”
PURA has previously fined CNG over pipeline safety. In an earlier case, regulators imposed a $25,000 penalty after a cap blew off a plastic pipe in Wethersfield, releasing gas for about 25 minutes and prompting officials to close Route 175.